Improvement of Midle Voltage Network Protection System at Kualanamu International Airport
Abstract
The electricity grid protection system at Kualanamu International Airport is urgently needed. The purpose of protection in addition to maintaining the reliability and stability of the electric power system also functions to detect disturbances, prevent damage to equipment (equipment & networks), protect humans and minimize outages in the event of a system disturbance. flight safety operations, services to passengers, operations, and equipment work at Kualanamu Airport. Safety or protection settings are based on the characteristics of the protection installed in the distribution system, which greatly affects working time, from the protection security area if there is a failure in the main protection. determine the setting of the overcurrent relay against overcurrent disturbances that may occur due to short circuit faults. To simplify the calculation of the disturbance analysis, it is simulated using the Electric Transient and Analysis Program (ETAP) Power Station12.6 software. The relay protection that is used and set is the overcurrent relay at the Kualanamu Airport Medium Voltage Network Sub Station. This relay functions to protect fault currents against ground-phase, ground-phase, ground-phase, and 3-phase. The protection relay setting refers to the provisions in force at PLN, namely for the interruption time of the 20 kV network disturbance at the substation from the time of a disturbance to the extinction of the electric arc by the opening of the power circuit breaker (PMT) the feeder is: less than or equal to 400 milliseconds and for ground-phase short circuit faults NGR12 maximum disconnection time of 500 milliseconds, NGR40 maximum disconnection time of 1000 milliseconds.
Keywords
Full Text:
PDFReferences
Arismunandar, A dan Kuwahara, S. (1972). Teknik Tenaga Listrik, Jilid III gardu induk. Jakarta : PT Pradnya Paramita Batubara, Supina. "Analisis perbandingan metode fuzzy mamdani dan fuzzy sugeno untuk penentuan kualitas cor beton instan." IT Journal Research and Development 2.1 (2017): 1-11.
Batubara, et al. (2018). "Penerapan Metode Certainty Factor Pada Sistem Pakar Diagnosa Penyakit Dalam." Seminar Nasional Royal (SENAR). Vol. 1. No. 1. Buku Kesepakatan Bersama Pengelolaan Sistem Proteksi Trafo-Penyulang 20 kV PT PLN(Persero)Penyaluran dan Pusat Pengatur Beban Jawa Bali Fitriani,
Hardinata, R. S. (2019). Audit Tata Kelola Teknologi Informasi menggunakan Cobit 5 (Studi Kasus: Universitas Pembangunan Panca Budi Medan). Jurnal Teknik dan Informatika, 6(1), 42-45.
Hendrawan, J., & Perwitasari, I. D. (2019). Aplikasi Pengenalan Pahlawan Nasional dan Pahlawan Revolusi Berbasis Android. JurTI (Jurnal Teknologi Informasi), 3(1), 34-40
Khairul, K., Haryati, S., & Yusman, Y. (2018). Aplikasi Kamus Bahasa Jawa Indonesia dengan Algoritma Raita Berbasis Android. Jurnal Teknologi Informasi dan Pendidikan, 11(1), 1-6.
Multa, L.P.,S.T.,M.Eng Aridani, Prima Restu (2013). Modul Pelatihan Etap. Yogyakarta, Universitas Gadjah Mada Buku Kesepakatan Bersama Pengelolaan Sistem Proteksi Trafo-Penyulang 20 kV PT PLN(Persero)Penyaluran dan Pusat Pengatur Beban Jawa Bali
Marsudi, D (2006). Operasi Sistem Tenaga Listrik. Yogyakarta, Graha Ilmu. Muhammad Arifai,
Muhammad Hadi Satria. (2017). Analisis Kestabilan Frekuensi dan Tegangan Sistem Tenaga Listrik PT Aneka Tambang(Persero) TBK UBPN Sulawesi Tenggara : Tugas Akhir Jurusan Teknik Elektro, Fakultas Teknik Universitas Hasanuddin Makasar
Suwarno, et al. (2021). Study Feasibility Analysis of Biodiesel Energy Processing Used Cooking Oil. Budapest International Research and Critics Institute-Journal (BIRCI-Journal). P. 7374-7386.
W., Rahim, R., Oktaviana, B., & Siahaan, A. P. U. (2017). Vernam Encypted Text in End of File Hiding Steganography Technique. Int. J. Recent Trends Eng. Res, 3(7), 214-219.
DOI: https://doi.org/10.33258/birci.v4i3.2655
Article Metrics
Abstract view : 26 timesPDF - 23 times
Refbacks
- There are currently no refbacks.

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.